Program Flowchart and Index
Page 9 of 15
Chapter 3 – Configuring the Inverter
The configuration of inverter parameters will depend on the specific functionality and performance required for
your application. The basic functionality of the board is designed to interface with a two pushbutton,
two-position (two-speed) momentary contact type pendant commonly used for crane and hoist applications. This
is the basis for the descriptions of the functions of the board presented in this manual. The setup in the table
below will result in infinitely variable speeds between the programmed MIN and MAX speeds. The defined
functions of the pushbuttons are as follows:
UP, first detent: UP – accelerate to minimum speed
UP, second detent: UP – increase speed while held, up to MAX speed (or go to second speed, see page 11)
DOWN, first detent: DOWN – accelerate to minimum speed (RESET fault when inverter is
STOPPED and in a fault state)
DOWN, second detent: DOWN – increase speed, up to MAX speed (or go to second speed, see page 11)
Pushing either the UP or DOWN pushbutton to the first position causes the inverter to go to the minimum
configured speed in that direction. Pushing that button further to its second position will cause speed to increase
in that direction. Releasing back to first position will hold that last speed. Releasing the pushbutton all the way
will cause the inverter to come to a stop. If that button is re-pressed to the first position before stop is reached,
that speed will be maintained. In order to achieve this basic functionality, the installation of the EzSQ C&H
program must be downloaded to the inverter through the use of Hitachi ProDriveNext software. The software is
available to download from our company website.
This program also will require a change in parameters that differ from factory default values, as described in the
following table. The application will also write to these parameters as needed.
Function Setting Comment
F002 Acceleration Time Note 1
Set a value between 1 and 3600 seconds, depending on application. If P031
is set to 03, acceleration is controlled by EzSQ. This is field adjustable.
F003
Note 1
Set a value between 1 and 3600 seconds, depending on application. If P031
is set to 03, deceleration will be controlled by EzSQ. This is field adjustable.
A001
07 Tells the inverter to read speed reference from EzSQ program. See note 3.
A002 Run Command 01 Tells the inverter to take the RUN command from the control terminals.
A004
Note 1
Depending on the motor limits and application requirements, set the
appropriate value, (Must be equal or greater than P120 parameter)
P120
Note 1
Usually the same value as A004. See note 3. This is field adjustable.
P110
Lower Frequency
Limit
Note 1
Lowest speed for continuous operation (MIN speed), usually 6 to 10 Hz or
so. This is the speed that will be commanded at the first pushbutton position.
See note 3. This is field adjustable.
B091
Stop Mode
Selection
00 For Non-Load Brake Hoist, or for traverse applications: 00 (factory default)
01 For Load Brake Hoist applications: 01 (free-run or coast to stop)
C001
Terminal 1
Function
56 WJ200 = [MI1]. See note 3.
no SJ700 Open Loop = [NO] No function
56 SJ700 Closed Loop = [MI1]. See note 3.